The Schneider Electric C10F6TM032 is a ComPacT NSX100F 4-pole circuit breaker with a 32 A thermal-magnetic TM-D trip unit. It is rated for distribution applications and provides overload (thermal) and short-circuit (magnetic) protection per EN/IEC 60947-2. The breaking capacity reaches 85 kA Icu at 240 V AC and 36 kA Icu at 415 V AC, making it suitable for high-fault panels where the upstream transformer can deliver substantial short-circuit current.
The 32 A rating at 40 °C is the continuous current the breaker can carry without tripping in a 40 °C ambient. The TM-D trip unit uses a thermal bimetal for overload and a magnetic coil for short-circuit — no electronic adjustment, so it is a fixed-curve device. The 85 kA Icu at 240 V AC is the maximum fault current it can safely interrupt at that voltage; at 415 V AC the rating drops to 36 kA Icu, which still covers most commercial and light industrial panelboards.
Front connections on both the line and load sides simplify busbar or cable routing in a panel. The 140 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. The toggle control provides a clear visual position indicator.