Skip to main content
Schneider Electric C10H3MA100

C10H3MA100 ComPacT NSX 100A MCCB, 70kA 415V AC Motor Protect

MPN C10H3MA100
Active

Schneider Electric ComPacT NSX, C10H3MA100, 3P 100A MCCB with magnetic trip unit, 70 kA Icu at 415 V AC, motor protection application.

$340.07 – $558.95 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10H3MA100 key specifications
ParameterValue
Control typeToggle
Trip unit typeMagnetic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10H3MA100 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

It is a 3-pole unit rated 100 A at 65 °C, with a breaking capacity of 70 kA Icu at 380/415 V AC per IEC 60947-2. The magnetic trip responds to short-circuit faults only — no thermal overload element — so motor overload protection must be handled separately by a thermal relay or motor protection relay upstream.

This H-frame breaker delivers 70 kA Icu at 415 V AC, 65 kA at 440 V, and 50 kA at 500 V. At 690 V AC it still holds 10 kA Icu. The high interrupting rating at typical 400 V industrial supply means it can be used as a main or feeder breaker in high-fault panels without cascading upstream. The magnetic trip unit (MA) provides instantaneous short-circuit protection only, with no adjustable time delay — coordination with downstream devices relies on the let-through energy (I²t) of the breaker itself.

Front connections for both line and load sides. IP40 enclosure protection and IK07 impact resistance suit panel-mounted installations in industrial environments.

Mechanical endurance is 50,000 cycles. Electrical durability varies with load: 50,000 cycles at 440 V at half rated current, 30,000 cycles at full rated current, and 10,000 cycles at 690 V at full rated current.

MPN
C10H3MA100