Skip to main content
Schneider Electric C10L4 — Miniature Circuit Breakers (MCB)

Schneider Electric C10L4 ComPacT NSX100L Basic Frame, 100A,

MPNC10L4
Obsolete

Schneider Electric ComPacT NSX100L basic frame, C10L4, 4 poles, 100 A frame rating at 40 °C, 150 kA Icu at 415 V AC, without trip unit.

$280.36 – $646.27Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10L4 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeBasic frame
Device applicationDistribution
C10L4 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity130 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)130 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 150 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10L4 — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)10000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 20000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 30000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 50000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)50000 cycles conforming to IEC 60947-2
C10L4 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeToggle
C10L4 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
C10L4 — Approvals
ParameterValue
StandardsEN/IEC 60947-2 UL 60947-4-1

Product details

What the breaking capacity means for your panel

The C10L4 is a ComPacT NSX100L basic frame — a 4-pole, 100 A rated (at 40 °C) air circuit breaker frame without a trip unit. The Ics (service breaking capacity) matches the Icu at 415 V — 150 kA — so you get full rated performance after a fault, not a derated service rating. For selectivity studies, that 150 kA at 415 V gives headroom downstream for smaller breakers to clear before this frame opens.

Standards and isolation suitability

Overvoltage category III covers fixed-installation distribution boards. The front face carries Class II shock protection, so no additional grounding of the enclosure face is needed.

Fixed-mount design for backplate installation. The 4-pole frame is 140 mm wide, 161 mm high, 86 mm deep — check your enclosure depth before committing to the panel layout. Connection pitch is 35 mm, with front-facing connections on both the upside and downside.

Durability and operating range

Mechanical durability is 50,000 cycles. Electrical durability varies with load: 30,000 cycles at 440 V AC at rated current, 50,000 cycles at half rated current. That is enough for a main distribution breaker that sees a few operations per day.

Frequently asked questions

What is C10L4's breaking capacity at 415 V?

The C10L4 carries a breaking capacity code L: 150 kA Icu at 415 V AC 50/60 Hz per IEC 60947-2. The Ics (service breaking capacity) is also 150 kA at that voltage.

What compliance documentation does Schneider provide for C10L4?

The C10L4 is certified to EN/IEC 60947-2 and UL 60947-4-1. It is marked as suitable for isolation per EN/IEC 60947-2 and carries pollution degree 3 per IEC 60664-1. The front face is Class II shock protection.

MPN