Skip to main content
Schneider Electric C10N32D040

C10N32D040 ComPacT NSX100N 40A 3P Circuit Breaker, 50kA 415V

MPN C10N32D040
Active

Schneider Electric ComPacT NSX series, C10N32D040, 3P circuit breaker, 40 A at 40 °C, MicroLogic 2.2 electronic trip unit, 50 kA Icu at 415 V AC, 105 mm width.

$283.91 – $816.32 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10N32D040 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C
Temp operating max70 °C

All specifications

C10N32D040 additional specifications
ParameterValue
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical life cycles50000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The C10N32D040 is a Schneider Electric ComPacT NSX100N frame circuit breaker with a MicroLogic 2.2 electronic trip unit, rated 40 A at 40 °C, 3-pole, and a breaking capacity code of N — 50 kA Icu at 415 V AC.

Mounting and integration into a distribution panel

Mounts on a backplate — not DIN rail — in either horizontal or vertical orientation, flat on the back. The 105 mm width, 161 mm height, and 86 mm depth fit the standard ComPacT NSX cutout; connection pitch is 35 mm. Both line and load connections are front-facing, so busbar or cable routing stays accessible inside the enclosure.

Electrical durability and thermal memory — what they mean for a motor or distribution load

Rated for 50,000 mechanical cycles and 30,000 electrical cycles at 440 V at full rated current (In). That's enough for a main breaker that sees a few operations per day over a 20-year panel life. The trip unit is electronic, not thermal-bimetal, so it holds calibration over temperature and is less prone to drift than a thermal-magnetic breaker.

Pollution degree 3 (IEC 60664-1) means it's rated for conductive pollution environments typical of industrial panels. Overvoltage category III suits fixed-installation distribution boards. Compliance documentation (declaration of conformity, CE marking) is available from the manufacturer's documentation portal.

MPN