Skip to main content
Schneider Electric C10N47E040 — Residual Current Breakers (RCCB/RCBO)

Schneider C10N47E040 ComPacT NSX100N 40A 4P, 50 kA 415 V

MPNC10N47E040
Obsolete

Schneider Electric ComPacT NSX NSX100N, 40 A at 40 °C, 4P, MicroLogic 7.2 E electronic trip unit, 50 kA Icu at 415 V AC, EN/IEC 60947-2.

$1,610.81 – $3,560.76Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N47E040 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10N47E040 — Electrical Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (operating cycles)50000 cycles
C10N47E040 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX100N
C10N47E040 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10N47E040 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10N47E040 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The Schneider Electric C10N47E040 is a ComPacT NSX100N moulded-case circuit breaker rated 40 A at 40 °C, 4-pole, fitted with a MicroLogic 7.2 E electronic trip unit. That trip unit gives you L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection in one package — no separate ground-fault relay needed for the distribution board. At 480 V AC it still holds 50 kA under UL 60947-4-1, so it crosses over into North American motor-circuit applications.

What the MicroLogic 7.2 E actually does in the panel

It logs time-stamped events, demand values, power quality, and min/max readings — data you'd normally need a separate power meter to pull. The 4-pole configuration has the neutral on the left, front-connected both top and bottom.

Frequently asked questions

What is the breaking capacity of C10N47E040 at 415 V?

50 kA Icu at 380/415 V AC per IEC 60947-2, which is the N-frame rating for the NSX100N.

Where can I buy C10N47E040?

Sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time.

MPN
C10N47E040