Skip to main content
Schneider Electric C10N47E100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C10N47E100 ComPacT NSX100N, 100 A, 90 kA

MPNC10N47E100
Obsolete

Schneider Electric ComPacT NSX, NSX100N, 100 A at 40 °C, 90 kA Icu at 240 V AC, MicroLogic 7.2 E trip unit, 4P, electronic.

$1,610.81 – $3,560.76Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N47E100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C10N47E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (operating cycles)50000 cycles
C10N47E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX100N
C10N47E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10N47E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10N47E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C10N47E100 is a Schneider Electric ComPacT NSX100N moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 100 A at 40 °C. At 415 V AC the breaking capacity is still 50 kA Icu, which covers most European industrial distribution panels. The trip unit offers L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — a full four-quadrant electronic trip that lets you coordinate selectivity downstream without sacrificing speed on hard faults. The LCD display and energy-metering capability (time-stamped histories, demand values, power quality) mean this breaker doubles as a panel-level power monitor, reducing the need for separate metering hardware.

Deployment context

What the durability numbers tell you

Mechanical durability is 50,000 cycles; electrical durability ranges from 50,000 cycles at 440 V at half rated current down to 10,000 cycles at 690 V at full rated current. For a distribution breaker that sees infrequent switching (unlike a contactor), these numbers are generous — the mechanical life will outlast the panel's service life in most installations.

Frequently asked questions

What is the breaking capacity of C10N47E100 at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What protection functions does the MicroLogic 7.2 E trip unit provide?

L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection.

Where can I buy C10N47E100 and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution, with availability and current pricing confirmed at quote time.

What compliance standards does C10N47E100 meet?

It complies with EN/IEC 60947-2 and UL 60947-4-1, with pollution degree 3 per IEC 60664-1.

MPN
C10N47E100