Schneider Electric C10N4TM032C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N4TM032C ComPacT NSX100N, 32 A, 50 kA

MPNC10N4TM032C
Active

Schneider Electric ComPacT NSX, NSX100N, circuit breaker, 4P, 32 A rated, TM-D thermal-magnetic trip unit, 50 kA Icu at 415 V AC, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N4TM032C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N4TM032C — Ratings
ParameterValue
Rated current (In)32 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N4TM032C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N4TM032C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N4TM032C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N4TM032C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N4TM032C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

ComPacT NSX100N, 32 A, 50 kA — what you're sourcing

The Schneider Electric C10N4TM032C is a ComPacT NSX100N circuit breaker, 4-pole, rated 32 A at 50 °C with a TM-D thermal-magnetic trip unit. It's designed for distribution duty (EN/IEC 60947-2, Category A), with suitability for isolation confirmed by the standard.

At 32 A, this breaker protects a 32 A feeder or load circuit — the TM-D trip provides thermal overload (L) and magnetic short-circuit (I) protection.

Physical integration and environment

Mounts on a backplate (flat on the back, horizontal or vertical). IP40 front-face protection (IK07 impact resistance) means it's suited for enclosed panel installation — not washdown environments.

Rated for 50,000 mechanical cycles and 30,000 electrical cycles at 440 V In (20,000 at 690 V In/2, 10,000 at 690 V In). That's the expected service life under rated load — relevant for a panel that sees regular switching, not just fault protection. The electrical durability figures assume the breaker is switched under load, not just used as a disconnect.

Frequently asked questions

What is the breaking capacity of C10N4TM032C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2.

What trip unit does C10N4TM032C use?

A TM-D thermal-magnetic trip unit rated 32 A at 50 °C, providing overload (L) and short-circuit (I) protection.

How do I get current pricing and availability for C10N4TM032C?

Submit an RFQ — we source this through independent distribution and confirm availability and current pricing at quote time.

What standards does C10N4TM032C comply with?

EN/IEC 60947-2 for circuit-breaker performance, IEC 60664-1 for pollution degree 3, and IEC 62262 for IK07 impact resistance. It is suitable for isolation per EN/IEC 60947-2.

MPN
C10N4TM032C