Breaking capacity and what it means for your panel
The C10N4TM050C delivers 90 kA Icu at 220/240 V AC, 50 kA at 380/415 V AC, and 36 kA at 500 V AC — all per IEC 60947-2. The 'N' breaking capacity code (50 kA at 415 V) positions it between the standard 'S' (36 kA) and high-performance 'H' (70 kA) frames in the NSX family.
Front connections top and bottom simplify busbar and cable routing in a distribution board. Width 140 mm, height 161 mm, depth 86 mm; the 35 mm connection pitch matches standard DIN-rail terminal blocks for outgoing circuits. IP40 enclosure protection keeps dust out; IK07 impact rating handles incidental tool strikes during panel work.