Skip to main content
Schneider Electric C10N4TM063C — Miniature Circuit Breakers (MCB)

Schneider Electric C10N4TM063C ComPacT NSX 63A 4P Circuit Br

MPNC10N4TM063C
Active

Schneider Electric ComPacT NSX circuit breaker, 4 poles, 63 A rated, TM-D thermal-magnetic trip unit, 50 kA breaking capacity at 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N4TM063C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N4TM063C — Ratings
ParameterValue
Rated current (In)63 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N4TM063C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N4TM063C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N4TM063C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N4TM063C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N4TM063C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

C10N4TM063C — ComPacT NSX 63 A, 4P, TM-D, 50 kA

The Schneider Electric C10N4TM063C is a ComPacT NSX100N circuit breaker, 4-pole, rated 63 A at 50 °C with a TM-D thermal-magnetic trip unit.

At 220/240 V AC the Icu jumps to 90 kA; at 690 V AC it drops to 10 kA. For a 415 V distribution board, the 50 kA figure sets the upstream fault level the breaker must clear — coordinate with a higher-rated upstream device if the prospective short-circuit current exceeds that. The 63 A continuous rating and the TM-D curve give you the LSI protection band for a feeder or a large submain.

The 140 mm width and 86 mm depth fit standard distribution panel layouts; the 35 mm connection pitch matches common busbar and terminal-block spacing. IP40 enclosure protection and IK07 impact resistance suit indoor distribution boards in clean industrial or commercial environments.

Durability and neutral protection

Mechanical durability rated at 50,000 cycles; electrical durability varies with load — 50,000 cycles at 440 V at half rated current, 30,000 at full rated current, and 10,000 at 690 V at full rated current. The 4-pole version (4D) provides neutral protection at 1 x Ir — fully rated neutral pole, not a switched-only neutral. Neutral position is left. No integrated earth-leakage protection; add a Vigi module if ground-fault detection is required.

Frequently asked questions

How do I get current pricing and availability for C10N4TM063C?

The C10N4TM063C is sourced and quoted to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time.

What is the breaking capacity of C10N4TM063C at 415 V?

The C10N4TM063C has a 50 kA Icu at 380/415 V AC 50/60 Hz conforming to EN/IEC 60947-2 (N breaking capacity code).

What standards does C10N4TM063C comply with?

The C10N4TM063C complies with EN/IEC 60947-2 and is suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

MPN