The TM-D technology gives you thermal protection (L) for overloads and magnetic protection (I) for short circuits, both adjustable on the trip unit face. At 690 V AC that figure drops to 10 kA Icu, so if your line-to-line voltage sits above 525 V, the available fault current needs to stay within that envelope.
The 4-pole body measures 161 mm high by 140 mm wide by 86 mm deep, with a 35 mm connection pitch between poles.
Certified to EN/IEC 60947-2, with suitability for isolation marked on the device. The IK07 impact rating means the enclosure withstands a 2 J hammer blow; the IP40 front face keeps tools and fingers out.