Skip to main content
Schneider Electric C10N6TM100C — Miniature Circuit Breakers (MCB)

C10N6TM100C ComPacT NSX100N MCCB, 100 A, 50 kA 415 V

MPNC10N6TM100C
Active

Schneider Electric ComPacT NSX100N, 4-pole MCCB, 100 A TM-D trip unit, 50 kA Icu at 415 V AC, toggle control, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10N6TM100C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C10N6TM100C — Ratings
ParameterValue
Rated current (In)100 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10N6TM100C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)50000 cycles at 440 V In/2 30000 cycles at 440 V In 20000 cycles at 690 V In/2 10000 cycles at 690 V In
Mechanical durability (cycles)50000 cycles
C10N6TM100C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10N6TM100C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10N6TM100C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10N6TM100C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C10N6TM100C is a Schneider Electric ComPacT NSX100N moulded-case circuit breaker with a 100 A thermal-magnetic trip unit (TM-D). It is a 4-pole, 50/60 Hz device rated for distribution duty in commercial and industrial panels. The 50 kA Icu at 415 V AC (per IEC 60947-2) gives it enough interrupting capacity for most secondary-distribution switchboards without needing a current-limiting upstream device. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection. The 100 A rating is at 50 °C ambient — no derating guesswork for a warm panel.

At 220/240 V it reaches 90 kA Icu; at 690 V it drops to 10 kA Icu. For a 400 V distribution board this breaker coordinates cleanly downstream of a higher-rated ComPacT NSX or NS frame — the 50 kA Icu at 415 V is the figure to use in a selectivity study per IEC 60947-2.

Integration notes

Dimensions are 161 mm high × 140 mm wide × 86 mm deep. Electrical durability is 50,000 cycles at 440 V at half rated current, 30,000 cycles at full rated current.

Frequently asked questions

What is the breaking capacity of C10N6TM100C at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

Where can I buy C10N6TM100C?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance standards does C10N6TM100C meet?

It complies with EN/IEC 60947-2, is suitable for isolation per that standard, and carries IP40 and IK07 ratings.

MPN
C10N6TM100C