Skip to main content
Schneider Electric C10R36M050

Schneider Electric C10R36M050 ComPacT NSX 50 A, 200 kA Icu

MPN C10R36M050
Active

Schneider Electric ComPacT NSX, NSX100R, circuit breaker, 3P, 50 A at 65 °C, 200 kA Icu at 415 V AC, MicroLogic 6.2 E-M electronic trip unit, motor protection.

$23.28 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C10R36M050 key specifications
ParameterValue
Control typeToggle
Display typeLCD display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz
Insulation voltage ui800 V AC 50/60 Hz
Breaking capacity200 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 200 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 45 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C

All specifications

C10R36M050 additional specifications
ParameterValue
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-40...85 °C
Pollution degreeclass 3
Depth86 mm
Width105 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationMotor protection
Operating temperature-25...70 °C

Product details

The Schneider Electric C10R36M050 is a ComPacT NSX circuit breaker from the NSX100R frame, fitted with a MicroLogic 6.2 E-M electronic trip unit and rated for motor protection at 50 A at 65 °C.

Above that ambient, derating applies per the manufacturer's curve. The MicroLogic 6.2 E-M provides L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground fault) protection, with selectable motor tripping classes 5, 10, 20, and 30. Class 10 is standard for general-purpose motor starting; class 20 or 30 accommodates high-inertia loads like fans or centrifuges that take longer to accelerate. At 690 V AC the rating drops to 45 kA Icu — still substantial for a 690 V motor feeder. The breaker carries a utilisation category A (non-selectively coordinated for short-circuit), so it is suited for standalone motor protection or as part of a cascaded system where the upstream device handles selectivity.

The 105 mm width and 161 mm height fit standard ComPacT NSX cutouts; depth is 86 mm. Five accessory slots are available for auxiliary contacts, shunt trips, or communication modules. The LCD display on the MicroLogic 6.2 E-M shows energy metering, demand values, and event logs — useful for commissioning and troubleshooting.

MPN