Schneider Electric C10V36M050 — Residual Current Breakers (RCCB/RCBO)

C10V36M050 ComPacT NSX 50A, 85kA Icu at 500V AC

MPNC10V36M050
Active

Schneider Electric ComPacT NSX circuit breaker, C10V36M050, 3-pole, 50 A rated at 65 °C, MicroLogic 6.2 E-M electronic trip unit, 85 kA Icu at 500 V AC.

$13.23Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10V36M050 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C10V36M050 — Electrical Ratings
ParameterValue
Rated current (In)50 A at 65 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10V36M050 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100HB1
C10V36M050 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10V36M050 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10V36M050 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C10V36M050 is a Schneider Electric ComPacT NSX circuit breaker, 3-pole, with a MicroLogic 6.2 E-M electronic trip unit rated at 50 A at 65 °C. It's built for motor protection, not just feeder duty — the E-M trip unit gives you adjustable overload (L), short-time (So), instantaneous (I), and ground-fault (G) protection curves, with motor tripping classes 10, 5, 20, and 30 selectable. The 85 kA Icu at 500 V AC is the interrupting rating that governs fault clearing in a motor branch circuit; at 690 V AC it still holds 75 kA Icu, which covers most industrial motor starters. The part sits in the ComPacT NSX family, so it shares the standard backplate mount, front connections, and the 105 mm wide footprint that fits a typical MCC bucket or panel layout.

Mounting and integration — backplate, front connections, 105 mm wide

The 105 mm width (W) and 161 mm height (H) with 86 mm depth (D) fit standard panel layouts. Overvoltage category III covers fixed-installation distribution boards.

Standards and approvals — EN/IEC 60947-2, IK07

The IK07 impact rating per IEC 62262 means the enclosure withstands a 2 J impact — enough for a tool drop in a panel. The LCD display on the trip unit shows metering data, protection settings, and event logs, which is useful during commissioning without needing a separate communication gateway.

Frequently asked questions

What is C10V36M050 used for?

It is a motor-protection circuit breaker with a MicroLogic 6.2 E-M trip unit. It protects motor branch circuits against overload, short-time short-circuit, instantaneous short-circuit, and ground faults, with selectable tripping classes 10, 5, 20, and 30.

Where can I buy C10V36M050?

The part is sourced and quoted to order through independent distribution. Submit an RFQ for current availability and pricing — confirmed at quote time.

What breaking capacity does C10V36M050 have at 690 V?

It is rated 75 kA Icu at 660/690 V AC 50/60 Hz per IEC 60947-2.