Specifications

C10V3MA025 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationMotor protection
C10V3MA025 — Ratings
ParameterValue
Rated current (In)25 A at 65 °C
Poles configuration3P
Breaking capacity85 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)85 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 80 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 75 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C10V3MA025 — Protection
ParameterValue
Trip unit technologyMagnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C10V3MA025 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C10V3MA025 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C10V3MA025 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C10V3MA025 — Specifications
ParameterValue
Trip unit protection functionsI

Product details

Overview

This 3-pole unit delivers an 85 kA ICu breaking capacity at 690 V AC, making it suitable for high-fault industrial motor branch circuits. The fixed-mount, front-connection package fits standard 35 mm terminal pitch and carries an IP20 finger-safe front face.

MPN