Skip to main content
Schneider Electric C10W36M080 — Residual Current Breakers (RCCB/RCBO)

Schneider C10W36M080 ComPacT NSX 80A MCCB, 100kA 690V

MPNC10W36M080
Active

Schneider Electric ComPacT NSX, C10W36M080, 3-pole MCCB, 80 A trip unit, 100 kA Icu at 690 V AC, MicroLogic 6.2 E-M electronic trip unit, motor protection.

$1,165.07Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C10W36M080 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C10W36M080 — Electrical Ratings
ParameterValue
Rated current (In)80 A at 65 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIII
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C10W36M080 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeCircuit breaker
Product range / familyComPacT
Device short nameNSX100HB2
C10W36M080 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C10W36M080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C10W36M080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C10W36M080 is a Schneider Electric ComPacT NSX100HB2 frame MCCB, 3-pole, with an 80 A MicroLogic 6.2 E-M electronic trip unit. Rated per EN/IEC 60947-2, utilisation category A (no intentional short-time delay for selective coordination).

Motor protection trip curve

The MicroLogic 6.2 E-M trip unit provides L (long-time overload), So (short-time short-circuit), I (instantaneous), and G (ground fault) protection. Motor tripping classes 5, 10, 20, and 30 are selectable — class 10 is the standard for standard induction motors, class 20 for high-inertia loads, class 30 for very heavy starts. The electronic trip unit also logs energy metering, demand values, and event histories via the integrated communication port.

Front connections top and bottom. 35 mm connection pitch matches busbar and cable lug spacing. Five accessory slots for auxiliary contacts, shunt trips, or communication modules. Pollution degree 3 (conductive pollution, typical in industrial panels), overvoltage category III. IK07 impact rating means it survives a 2 J hammer blow — fine for a machine-mounted enclosure.

Frequently asked questions

What is the breaking capacity of C10W36M080?

100 kA Icu at 500 V AC, 525 V AC, and 660/690 V AC 50/60 Hz per IEC 60947-2.

What trip unit is fitted on C10W36M080?

MicroLogic 6.2 E-M electronic trip unit, rated 80 A at 65 °C, with L, So, I, and G protection and selectable motor tripping classes 5, 10, 20, and 30.

Where can I buy C10W36M080?

Sourced and quoted to order against an RFQ through independent distribution; availability and current pricing confirmed at quote time.

MPN
C10W36M080