Skip to main content
Schneider Electric C114100LS — Miniature Circuit Breakers (MCB)

Schneider Electric C114100LS ComPacT NSXm 100NA Switch Disco

MPNC114100LS
Active

Schneider Electric ComPacT NSXm 100NA, switch disconnector, 4 poles, Ith 100 A at 40 °C, 440 V AC, EverLink lugs, toggle control, IP40, IK07.

$264.70Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

C114100LS — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeSwitch disconnector
Device applicationDistribution

Ratings

C114100LS — Ratings
ParameterValue
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Utilisation categoryAC-22A AC-23A

Protection

C114100LS — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-3
Electrical durability (cycles)AC-22A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-23A: 20000 cycles 440 V AC 50/60 Hz Ie/2 AC-22A: 10000 cycles 440 V AC 50/60 Hz Ie AC-23A: 10000 cycles 440 V AC 50/60 Hz Ie
Mechanical durability (cycles)20000 cycles

Mechanical

C114100LS — Mechanical
ParameterValue
Mounting support35 mm symmetrical DIN rail Backplate
Mounting modeFixed
Control typeToggle
Terminal connection type1 Everlink lug wire size 2.5...70 mm², flexible copper 1 Everlink lug wire size 2.5...95 mm², rigid or stranded aluminium/copper
Contact position indicatorYes

Environmental

C114100LS — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1

Approvals

C114100LS — Approvals
ParameterValue
StandardsEN/IEC 60947-1 EN/IEC 60947-3

Product details

The Schneider Electric C114100LS is a ComPacT NSXm 100NA switch disconnector, 4 poles, rated 100 A in both AC-22 and AC-23 utilisation categories at 440 V AC 50/60 Hz. It is suited for isolation per EN/IEC 60947-3, with a visible break indicator and toggle control. The 100 A thermal current (Ith) at 40 °C means it handles full-rated resistive and moderately inductive loads without derating in a 40 °C panel ambient.

Ratings and fit

Rated operational current is 100 A in both AC-22 (switching mixed resistive and inductive loads, including moderate overloads) and AC-23 (switching motors or other highly inductive loads). That 100 A holds at 440 V AC — no derating needed for the voltage step. Short-time withstand (Icw) is 1500 A for 1 s or 3 s, and 335 A for 20 s, which covers downstream fault clearing coordination. Short-circuit making capacity (Icm) is 2.13 kA as a stand-alone switch-disconnector, or 150 kA with an upstream protection circuit breaker — so it can be paired with a fast-acting breaker upstream for high-fault-current installations. Insulation coordination: rated impulse withstand voltage (Uimp) 8 kV, pollution degree 3 per IEC 60664-1, rated insulation voltage (Ui) 800 V AC. That puts it in the standard industrial panel category — no special creepage or clearance needed for most 400 V distribution.

Mounting and environment

Mounts on 35 mm symmetrical DIN rail or a backplate. Fixed mounting mode, 108 mm wide, 137 mm tall, 80 mm deep — fits a standard 4-pole disconnector footprint. Connection pitch 27 mm, terminals accept EverLink lugs: 2.5…70 mm² flexible copper, or 2.5…95 mm² rigid/stranded aluminium/copper. IP40 front face, IK07 impact resistance. Operating temperature -25…70 °C, storage -50…85 °C.

Frequently asked questions

Where can I buy C114100LS?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is C114100LS used for?

It is a switch disconnector for distribution applications — isolating and switching loads up to 100 A at 440 V AC in AC-22 (mixed loads) or AC-23 (motor/inductive) circuits. Suited for isolation per EN/IEC 60947-3, with a visible break indicator.

What compliance documentation does Schneider provide for C114100LS?

The part is certified to EN/IEC 60947-1 and EN/IEC 60947-3. It carries IP40 and IK07 protection ratings, and is rated for pollution degree 3 per IEC 60664-1. Electrical shock protection class II. For specific RoHS/REACH/UL documentation, request the compliance certificate with your RFQ.