Rated at 25 A (40 °C) with a 16 kA interrupting capacity at 415 V AC (performance level E), it uses an electronic MicroLogic 4.1 trip unit that provides adjustable earth-leakage sensitivity from 30 mA to 5 A, class A or AC. This is the part to specify when a distribution panel needs both short-circuit and ground-fault protection on a single DIN-rail-mountable footprint.
The 9-module pitch (108 mm wide, 144 mm high, 80 mm deep) fits standard distribution board cutouts. Front-facing connections top and bottom; the Everlink lug terminals accept 2.5–95 mm² rigid aluminium/copper or 2.5–70 mm² fine-stranded copper. Connection pitch is 35 mm with spreaders, 27 mm without — plan your busbar or cable routing accordingly.