Skip to main content
Schneider Electric C11E6TM040B — Miniature Circuit Breakers (MCB)

Schneider C11E6TM040B ComPacT NSXm 40A 4P 16kA Circuit Break

MPNC11E6TM040B
Active

Schneider Electric, ComPacT NSXm, MCCB, C11E6TM040B, 40A, 4P, 16kA at 415V AC, thermal-magnetic TM-D trip unit, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E6TM040B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E6TM040B — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E6TM040B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E6TM040B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E6TM040B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E6TM040B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E6TM040B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E6TM040B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The Schneider Electric C11E6TM040B is a ComPacT NSXm moulded-case circuit breaker (MCCB) with a 40 A thermal-magnetic TM-D trip unit, 4 poles, and a 16 kA breaking capacity at 415 V AC (performance level E). The TM-D trip unit is thermal-magnetic: the thermal bimetal handles overload protection (inverse-time curve), and the magnetic coil handles short-circuit instantaneous tripping. At 40 A and 40 °C ambient, it's sized for feeder or branch protection on 50/60 Hz AC networks.

The lifecycle stage is listed as current — this is an active-production part within the ComPacT NSXm family. No end-of-life notice or successor has been published.

Mounts on a backplate (not DIN rail) in either horizontal or vertical orientation, flat on the back. At 137 mm high, 108 mm wide, 80 mm deep, and occupying 12 module pitches at 9 mm each, it fits standard panel cutouts for the NSXm frame. Connection terminals accept compression lugs or busbars; front-connect both top and bottom simplifies busbar stacking in multi-breaker panels.

Rated IP40 (finger protection) and IK07 (impact resistance). Humidity range 0–95%.

Frequently asked questions

How do I get current pricing and availability for C11E6TM040B?

Submit an RFQ against this part. Pricing and stock are confirmed at quote time through independent distribution channels — no automated stock figure is published here.

What is the closest alternative to C11E6TM040B in the ComPacT family?

Within the ComPacT NSXm range, a 40 A 4P breaker with a different breaking capacity (e.g., 25 kA or 36 kA) or a different trip unit (Micrologic electronic) would be the parametric alternative. No pin-compatible drop-in exists outside the same NSXm frame; the TM-D trip unit and 16 kA E performance level define this variant.

What is C11E6TM040B's listed range?

It belongs to the ComPacT range, specifically the ComPacT NSXm sub-family — a compact MCCB line for distribution applications.

What colour is C11E6TM040B?

Grey (RAL 7016).

What compliance documentation does Schneider provide for C11E6TM040B?

The breaker is certified to EN/IEC 60947-2, rated for isolation per that standard, and carries pollution degree 3 and overvoltage category III ratings. RoHS and REACH declarations are typically available from Schneider's documentation portal for the ComPacT NSXm series.

MPN