Schneider Electric C11E6TM050B — Miniature Circuit Breakers (MCB)

Schneider Electric C11E6TM050B ComPacT NSXm 50A 4P MCCB, 16

MPNC11E6TM050B
Active

Schneider Electric ComPacT NSXm, C11E6TM050B, 4P MCCB, 50 A TM-D thermal-magnetic trip, 16 kA at 415 V AC, IEC 60947-2, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E6TM050B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E6TM050B — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E6TM050B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E6TM050B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E6TM050B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E6TM050B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E6TM050B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E6TM050B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Rated to IEC 60947-2, Category A — no intentional short-time delay, so it's a straightforward feeder or branch protector, not a main breaker coordinating with downstream devices on a selective scheme. The 4P (four-pole) configuration with neutral left means all four poles switch and protect, including the neutral — standard for TN-S or TT systems where you need full isolation. The TM-D trip combines a thermal bimetal for overload protection and a magnetic coil for short-circuit; no earth-leakage module inside, so if you need ground-fault protection, you add a Vigi module externally. Mounts on a backplate, not a DIN rail — the 108 mm width and 137 mm height fit the ComPacT NSXm footprint. The grey RAL 7016 colour is the standard NSXm finish.

The IEC 60947-2 listing covers most global markets except North America (where UL 489 would apply — this part is not UL listed).

Integration notes

Front connection top and bottom — compression lug or busbar, 35 mm pitch with spreaders, 27 mm without. That's the standard NSXm terminal arrangement; no special adapter needed for most panel layouts. The 12-module 9 mm pitch width (108 mm) means it occupies 12 positions on a standard backplate grid. Toggle control, flag indicator for auxiliary contact presence. Operating altitude 2000 m without derating, 5000 m with derating; if your site is above 2000 m, factor the derating curve.

Frequently asked questions

Where can I buy C11E6TM050B and get a price?

The C11E6TM050B is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of C11E6TM050B?

Performance level E: 16 kA at 415 V AC, per IEC 60947-2. That is the maximum fault current the breaker can safely interrupt at that voltage.

What standards does C11E6TM050B comply with?

It is designed and tested to EN/IEC 60947-2, the international standard for low-voltage moulded-case circuit breakers. It also meets IEC 60664-1 for pollution degree 3 and IEC 60529 for IP40 protection.

MPN