Skip to main content
Schneider Electric C11E6TM040L — Miniature Circuit Breakers (MCB)

Schneider C11E6TM040L ComPacT NSXm 40A 4P MCCB, 16kA 415V

MPNC11E6TM040L
Active

Schneider Electric ComPacT NSXm, 4P, 40 A at 40 °C, TM-D thermal-magnetic trip, 16 kA at 415 V AC, IP40, grey (RAL 7016).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E6TM040L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E6TM040L — Ratings
ParameterValue
Rated current (In)40 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E6TM040L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11E6TM040L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E6TM040L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E6TM040L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E6TM040L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
C11E6TM040L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 4-pole form with neutral left handles three-phase-plus-neutral circuits common in European and IEC distribution. The 108 mm width (12 x 9 mm pitches) fits standard enclosure cutouts. IP40 enclosure protection and IK07 impact resistance suit clean indoor panel environments.

Trip unit and coordination

The TM-D thermal-magnetic trip provides fixed thermal protection (inverse-time) and fixed magnetic instantaneous pickup. Electrical endurance is 20,000 cycles at 440 V In/2, dropping to 5,000 cycles at 690 V In. These figures govern maintenance intervals in high-cycle applications like conveyor or pump panels.

Frequently asked questions

What is the breaking capacity of C11E6TM040L?

16 kA at 415 V AC (performance level E) per IEC 60947-2. This is the maximum fault current the breaker can safely interrupt at that voltage.

Where can I buy C11E6TM040L?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your quantity and delivery target.

What wire sizes does the C11E6TM040L terminal accept?

Everlink lugs accept 2.5 to 95 mm² rigid or stranded aluminium/copper, and 2.5 to 70 mm² flexible copper.

MPN
C11E6TM040L