Skip to main content
Schneider Electric C11E6TM080B — Miniature Circuit Breakers (MCB)

Schneider Electric C11E6TM080B ComPacT NSXm 80A 4P Thermal-M

MPNC11E6TM080B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 80 A at 40 °C, 4P, TM-D thermal-magnetic trip unit, 16 kA at 415 V AC, EN/IEC 60947-2, grey (RAL 7016).

$452.30Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11E6TM080B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11E6TM080B — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11E6TM080B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11E6TM080B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11E6TM080B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11E6TM080B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11E6TM080B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 16 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11E6TM080B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

80 A, 4-pole thermal-magnetic breaker for distribution panels

The Schneider Electric C11E6TM080B is a ComPacT NSXm circuit breaker rated 80 A at 40 °C, with a TM-D thermal-magnetic trip unit and 4 poles (4P). Mounts on a backplate with front connections for compression lugs or busbars. The 108 mm width occupies 12 module pitches at 9 mm, so panel layout is straightforward — it fills a standard 12-module DIN-rail space. The grey RAL 7016 housing is the standard NSXm colour.

If your panel runs hotter, expect derating — the TM-D thermal element responds to ambient temperature. Utilization category A means it is not intended for frequent switching of motor loads — it is a distribution breaker, not a motor-protective device. The TM-D trip unit combines a thermal bimetal for overload protection and a magnetic coil for short-circuit protection. The D curve provides a higher magnetic trip threshold than B or C curves, suited for loads with moderate inrush like small transformers or capacitor banks. Earth-leakage protection is not built in — add a separate RCD if needed.

Panel integration and compliance

Rated IP40 and IK07 — protected against tools >1 mm and impact energy 2 J. Suitable for indoor panel mounting. Compliant with EN/IEC 60947-2, the standard for low-voltage circuit breakers. Mechanical durability is 20,000 cycles; electrical durability is 20,000 cycles at 440 V at In/2, and 10,000 cycles at 440 V at In.

Frequently asked questions

What is the breaking capacity of C11E6TM080B?

16 kA at 415 V AC, performance level E. This is the maximum fault current the breaker can safely interrupt at that voltage.

What trip unit does C11E6TM080B use?

A TM-D thermal-magnetic trip unit. The thermal element handles overloads; the magnetic coil handles short-circuits with a D-curve characteristic.

What standards does C11E6TM080B comply with?

EN/IEC 60947-2, the standard for low-voltage circuit breakers. It is also suitable for isolation per that standard.

Where can I buy C11E6TM080B and get current pricing?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

MPN