Schneider Electric C11H6TM025B — Miniature Circuit Breakers (MCB)

Schneider Electric C11H6TM025B ComPacT NSXm 4P 25A, 70 kA 41

MPNC11H6TM025B
Active

Schneider Electric ComPacT NSXm, circuit breaker, 4P, 25 A at 40 °C, TM-D thermal-magnetic trip unit, 70 kA at 415 V AC, grey (RAL 7016), IP40, IK07.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H6TM025B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H6TM025B — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H6TM025B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H6TM025B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H6TM025B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H6TM025B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H6TM025B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H6TM025B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What this 4-pole 25 A breaker is and where it fits

The Schneider Electric C11H6TM025B is a ComPacT NSXm moulded-case circuit breaker (MCCB) from the ComPacT range, built for distribution panels and sub-distribution boards. It's a 4-pole (4P) unit rated 25 A at 40 °C, with a thermal-magnetic TM-D trip unit — so the thermal element handles overloads and the magnetic element handles short-circuits, no external trip module needed. The 70 kA breaking capacity at 415 V AC (performance level H) means it can safely interrupt fault currents up to that level without upstream fuses or a bigger breaker — that's the kind of headroom you want when you're coordinating a panel and don't want a fault to cascade.

Ratings that decide the fit

The 25 A rating is at 40 °C ambient — if your panel runs hotter, you'll need to derate, but that's standard for any thermal-magnetic breaker. The 70 kA at 415 V AC is the interrupting rating (Icu) under IEC 60947-2, category A (no intentional short-time delay). That's a high-interrupting version (the 'H' in NSXm 63H), so it's suited for high-fault-current locations like near a transformer or a large service entrance. Pollution degree 3 (IEC 60664-1) means it's rated for conductive pollution or dry non-conductive pollution that becomes conductive — typical for industrial panels that aren't sealed clean rooms. Overvoltage category III means it's designed for fixed installations downstream of the main distribution board.

Frequently asked questions

Where can I buy C11H6TM025B?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C11H6TM025B?

The interrupting rating is 70 kA at 415 V AC (performance level H), per EN/IEC 60947-2.

What standards does C11H6TM025B comply with?

It complies with EN/IEC 60947-2, and is suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

Does C11H6TM025B include earth-leakage protection?

No, it does not include earth-leakage protection — the trip unit is thermal-magnetic only (TM-D).

MPN