Skip to main content
Schneider Electric C11H6TM025L — Miniature Circuit Breakers (MCB)

C11H6TM025L ComPacT NSXm 4P 25A 70kA MCCB, EN/IEC 60947-2

MPNC11H6TM025L
Active

Schneider Electric ComPacT NSXm, 4-pole, 25 A thermal-magnetic, 70 kA at 415 V AC, EN/IEC 60947-2, grey (RAL 7016).

$273.24Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H6TM025L — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H6TM025L — Ratings
ParameterValue
Rated current (In)25 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H6TM025L — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H6TM025L — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H6TM025L — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H6TM025L — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H6TM025L — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H6TM025L — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What the 70 kA breaking capacity means for your panel

The C11H6TM025L is a 4-pole ComPacT NSXm MCCB rated 25 A at 40 °C with a high-performance (H) breaking capacity of 70 kA at 415 V AC. It carries a Category A utilisation rating, meaning it is not intended for current-limiting coordination with downstream breakers in a cascaded scheme; selectivity must be engineered at the system level.

Trip unit and terminal fit

The fixed TM-D thermal-magnetic trip unit provides inverse-time overload protection (thermal bimetal) and instantaneous short-circuit protection (magnetic coil). At 25 A and 40 °C ambient, no derating is needed for most panel environments up to that temperature. The Everlink terminals accept copper or aluminium conductors from 2.5 to 95 mm² (rigid/stranded) and flexible copper up to 70 mm² — a wide enough range to handle both feed-through and downstream tap conductors without lug adapters. Connection pitch is 35 mm with spreaders, 27 mm without; the 12-module 9 mm pitch width (108 mm) occupies standard DIN-rail or backplate mounting.

Integration and environmental limits

Operating altitude is 2000 m without derating, 5000 m with derating — relevant for high-altitude installations where air density reduces arc-quenching effectiveness.

Frequently asked questions

What is the breaking capacity of C11H6TM025L?

The C11H6TM025L has a high-performance (H) breaking capacity of 70 kA at 415 V AC, certified to EN/IEC 60947-2.

What wire sizes does the C11H6TM025L terminal accept?

The Everlink terminals accept 2.5 to 95 mm² rigid or stranded aluminium/copper, and 2.5 to 70 mm² flexible copper.

Where can I buy C11H6TM025L and get current pricing?

The C11H6TM025L is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What compliance standards does C11H6TM025L meet?

The C11H6TM025L is certified to EN/IEC 60947-2 for low-voltage switchgear and controlgear. It carries an IP40 front face (IEC 60529), IK07 impact rating (IEC 62262), and Pollution Degree 3 (IEC 60664-1).

MPN