Skip to main content
Schneider Electric C11H6TM050B — Miniature Circuit Breakers (MCB)

Schneider C11H6TM050B ComPacT NSXm 4P 50A 70kA MCCB

MPNC11H6TM050B
Active

Schneider Electric ComPacT NSXm, C11H6TM050B, 4P 50A TM-D thermal-magnetic MCCB, 70 kA at 415 V AC, grey RAL 7016.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H6TM050B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H6TM050B — Ratings
ParameterValue
Rated current (In)50 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H6TM050B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C11H6TM050B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H6TM050B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H6TM050B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H6TM050B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 660...690 V AC 50/60 Hz conforming to IEC 60947-2
C11H6TM050B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

This is the figure that governs coordination with upstream switchgear; a standard 25 kA MCCB would cascade failure here. The 4-pole (4P) configuration with neutral on the left and front-connect terminals (compression lug or busbar) suits it for three-phase plus neutral panels where all poles are switched and protected. IP40 front face and IK07 impact rating mean it's safe in a locked enclosure but not washdown — keep it dry.

Mounts on a backplate (not DIN rail) — 12 module pitches at 9 mm each, so it occupies 108 mm of panel width. Height is 137 mm, depth 80 mm. Connection pitch is 35 mm with spreaders, 27 mm without. Can be mounted horizontally or vertically flat on the backplate. Pollution degree 3 (IEC 60664-1) means it's rated for conductive dust environments typical in industrial panels.

Frequently asked questions

How do I get current pricing and availability for C11H6TM050B?

Submit an RFQ through this listing. Pricing and stock are confirmed at quote time against your order quantity and delivery window.

What compliance documentation does this brand provide for C11H6TM050B?

The breaker is designed and tested to EN/IEC 60947-2. A Declaration of Conformity and test certificates are available from Schneider Electric upon request.

What is the interrupting rating of C11H6TM050B?

70 kA at 415 V AC (H performance level) per IEC 60947-2.

MPN
C11H6TM050B