ComPacT NSXm 4P 32 A — panel-builder commissioning notes
The breaker is listed as current-production (active lifecycle stage) and complies with EN/IEC 60947-2. Mounting is on a backplate, not a DIN rail — the 108 mm width and 137 mm height occupy 12 module pitches of 9 mm. Connection pitch is 35 mm with spreaders, 27 mm without. Terminals accept compression lugs or busbars, with both upside and downside connections on the front face. IP40 enclosure protection and IK07 impact resistance suit it for panel interiors where tools or debris might strike the front face.
Electrical durability and application context
Electrical durability is rated at 20,000 cycles at 440 V at In/2, and 10,000 cycles at 440 V at In; mechanical durability is 20,000 cycles. These figures define the maintenance interval for a panel builder planning a 10-year service life. Operating altitude is 2000 m without derating, 5000 m with derating. Relative humidity range is 0 to 95 %. Network frequency is 50/60 Hz. The neutral position is left, and the control type is toggle. No earth-leakage protection is integrated — if ground-fault detection is required, an external module or separate RCD must be added downstream.