Skip to main content
Schneider Electric C11H6TM080B — Miniature Circuit Breakers (MCB)

Schneider Electric C11H6TM080B ComPacT NSXm 80A 4P Thermal-M

MPNC11H6TM080B
Obsolete

Schneider Electric ComPacT NSXm, circuit breaker, 80 A at 40 °C, 4P, TM-D trip unit, 70 kA 415 V AC, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C11H6TM080B — Identification
ParameterValue
Product nameComPacT NSXm
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C11H6TM080B — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration4P
Rated operational voltage (Ue)440 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C11H6TM080B — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In
Mechanical durability (cycles)20000 cycles
C11H6TM080B — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlag (green) for presence of auxiliary contacts
Number of 9 mm pitches12 module
C11H6TM080B — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C11H6TM080B — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C11H6TM080B — Electrical
ParameterValue
[Icu] rated ultimate short-circuit breaking capacity100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
[Ics] rated service short-circuit breaking capacity100 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
C11H6TM080B — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

Part identification and key ratings

The C11H6TM080B is a Schneider Electric ComPacT NSXm moulded-case circuit breaker (MCCB) rated 80 A at 40 °C, 4-pole, with a TM-D thermal-magnetic trip unit. It carries a 70 kA breaking capacity at 415 V AC (performance level H), making it suitable for distribution boards where high fault-current headroom is required per EN/IEC 60947-2.

The 80 A rating at 40 °C is the continuous current the breaker carries without tripping in a 40 °C ambient — derate for higher enclosure temperatures.

Deployment context

Mounts on a backplate in horizontal or vertical orientation; the 108 mm width (12 module pitches) fits standard DIN-rail enclosures with a backplate adapter. Front connections accept compression lugs or busbars.

Frequently asked questions

What is the breaking capacity of C11H6TM080B?

The C11H6TM080B has a 70 kA breaking capacity at 415 V AC (performance level H), compliant with EN/IEC 60947-2.

What trip unit does C11H6TM080B use?

It uses a TM-D thermal-magnetic trip unit rated 80 A at 40 °C, with fixed overload and short-circuit protection curves.

What compliance documentation does C11H6TM080B carry?

The breaker is compliant with EN/IEC 60947-2, suitable for isolation per that standard, and carries pollution degree 3 and overvoltage category III ratings per IEC 60664-1.

MPN