Skip to main content
Schneider Electric C160N35EFM — Miniature Circuit Breakers (MCB)

C160N35EFM ComPacT NS 1600A MCCB, MicroLogic 5.0 E, 85 kA

MPNC160N35EFM
Active

Schneider Electric ComPacT NS new generation, C160N35EFM, 3P 1600 A MCCB with MicroLogic 5.0 E electronic trip unit, 85 kA Icu at 240 V AC, manually operated, fixed mount, IP40.

$3,364.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C160N35EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C160N35EFM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160N35EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C160N35EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C160N35EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C160N35EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C160N35EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C160N35EFM is a 3-pole ComPacT NS new generation MCCB rated 1600 A at 50 °C with a MicroLogic 5.0 E electronic trip unit. That trip unit provides L (long-time overload), S (short-time short-circuit), and I (instantaneous) protection curves, plus integrated energy metering — so it serves as both the main distribution breaker and a power-monitoring point in one package. The 85 kA Icu at 240 V AC (50 kA at 415 V, 30 kA at 690 V) tells you it can interrupt fault currents up to that level without upstream fuses, sized for high-fault-capacity industrial switchboards. The 1600 A frame covers large transformer feeds, busway risers, or generator mains.

Deployment context

Fixed-mount, backplate installation with front-connect terminals — standard for distribution switchboards where the breaker stays in place and cables land on the front face. The 210 mm width, 327 mm height, and 147 mm depth fit typical ComPacT NS cutouts; the 70 mm connection pitch matches busbar drilling patterns for 1600 A class. IP40 enclosure protection means it is suited for indoor panel environments, not washdown areas. Manually operated, no motor mechanism — intended for infrequent switching or as a main disconnect.

IK07 impact resistance and IP40 ingress protection. The MicroLogic 5.0 E trip unit includes thermal memory (20 min) for accurate overload protection after a trip event.

Frequently asked questions

Where can I buy C160N35EFM and how do I get a price?

This part is sourced through independent distribution channels. Submit an RFQ — we confirm availability and current pricing at quote time. No stock count or price is published here because both fluctuate with market conditions.

What is C160N35EFM's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 240 V it is 85 kA; at 690 V it is 30 kA.

What protection functions does the MicroLogic 5.0 E trip unit provide?

L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection, plus integrated energy metering. The trip unit is electronic, rated 1600 A at 50 °C.

MPN