Schneider Electric ComPacT NS1600N new generation, basic frame C160N4WM, 1600 A at 50 °C, 50 kA Icu at 415 V AC, 4 poles, withdrawable, manually operated, without control unit.

$2,734.08Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C160N4WM — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeBasic frame
Device applicationDistribution
C160N4WM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160N4WM — Protection
ParameterValue
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles 690 V AC 50/60 Hz In conforming to IEC 60947-2 2000 cycles 690 V AC 50/60 Hz In/2 conforming to IEC 60947-2 2000 cycles 440 V AC 50/60 Hz In conforming to IEC 60947-2 5000 cycles 440 V AC 50/60 Hz In/2 conforming to IEC 60947-2
Mechanical durability (cycles)10000 cycles conforming to IEC 60947-2
C160N4WM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeWithdrawable
Control typeManually operated
C160N4WM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
C160N4WM — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What this frame is — and what it is not

The C160N4WM is a ComPacT NS1600N basic frame — the structural and switching core of a 1600 A air circuit breaker, without a trip unit or electronic control module. Rated 1600 A at 50 °C, it carries 50 kA Icu at 415 V AC (50/60 Hz) and 85 kA Icu at 240 V AC, per IEC 60947-2. The 4-pole, withdrawable chassis mounts to a backplate with a 70 mm connection pitch, neutral on the left. You add the protection relay separately; this is the rugged skeleton for a distribution main or heavy feeder in a mining or industrial switchboard.

Breaking capacity — what the N rating means for your fault level

At 415 V the ultimate breaking capacity (Icu) is 50 kA, and the service breaking capacity (Ics) holds at 37 kA.

Withdrawable chassis — panel integration and maintenance

The withdrawable design lets the breaker rack out of the cassette for inspection, testing, or swap without disconnecting the main bus. Mounts to a backplate; the 70 mm connection pitch aligns with standard busbar drilling. The 306 mm width, 260 mm height, and 147 mm depth fit standard ComPacT NS630b...1600 new-generation cubicle cutouts.

Sourcing this frame for a BOM line

Because the C160N4WM is an active, current-production Schneider frame, it is sourced through standard industrial distribution channels. No minimum order quantity is imposed by the supply chain; the part is quoted to order for a single unit or a panel-build quantity.

Frequently asked questions

What is the closest alternative to C160N4WM in the ComPacT family?

The closest sibling is the fixed-mount version of the same NS1600N frame (order code differs by mounting suffix). The withdrawable chassis is the deciding difference — if your cubicle is wired for a fixed cassette, the fixed version saves cost and panel space. Both share the same 1600 A rating and 50 kA Icu at 415 V.

MPN