Schneider Electric C160N45EFM — Miniature Circuit Breakers (MCB)

Schneider Electric C160N45EFM ComPacT NS, 1600 A, 4P, MicroL

MPNC160N45EFM
Active

Schneider Electric ComPacT NS new generation, C160N45EFM, 4-pole molded case circuit breaker, 1600 A, MicroLogic 5.0 E electronic trip unit, 85 kA Icu at 240 V AC.

$3,809.10Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C160N45EFM — Identification
ParameterValue
Product nameComPacT NS new generation
Product rangeComPacT
Product range (series)ComPacT NS630b...1600 new generation
Product/component typeCircuit breaker
Device applicationDistribution
C160N45EFM — Ratings
ParameterValue
Rated current (In)1600 A at 50 °C
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 40 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)37 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 37 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)8 kV conforming to IEC 60947-2
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory B
Overvoltage categoryIII
C160N45EFM — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)1000 cycles at 690 V In 2000 cycles at 690 V In/2 2000 cycles at 440 V In 5000 cycles at 440 V In/2
Mechanical durability (cycles)10000 cycles
C160N45EFM — Mechanical
ParameterValue
Mounting supportBackplate
Mounting modeFixed
Control typeManually operated
Local signalling/indication4 LEDs (red) for fault indication 1 LED (yellow) for overload
C160N45EFM — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947
Relative humidity0...95 %
C160N45EFM — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C160N45EFM — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.4...1 x In
Trip unit protection functionsLSI

Product details

The C160N45EFM is a 4-pole ComPacT NS new generation molded case circuit breaker rated 1600 A at 50 °C, with a MicroLogic 5.0 E electronic trip unit that provides L (long-time overload), S (short-time short-circuit), and I (instantaneous short-circuit) protection. The IEC 60947-2 Category B utilization confirms it is designed for selectivity in distribution, not just cable protection. At 147 mm deep, 280 mm wide, and 327 mm tall, this fixed-mount breaker bolts to a backplate with a 70 mm connection pitch. The front-facing connections (upside and downside) simplify busbar or cable routing in a switchboard — no rear-access required. IP40 front face and IK07 impact rating handle the usual panel environment; pollution degree 3 means it tolerates conductive dust in industrial enclosures.

Deployment context

This breaker is sized for main or feeder protection in a 1600 A distribution switchboard — think a factory main incoming, a large motor control center, or a data-center PDU. The MicroLogic 5.0 E trip unit includes an energy meter (type of measurement: energy meter), so it doubles as a revenue-grade metering point without an extra CT cabinet. The LCD display shows real-time current, energy, and trip data locally. Mechanical durability is 10,000 cycles; electrical durability ranges from 1,000 cycles at 690 V In up to 5,000 cycles at 440 V In/2. That is typical for a distribution breaker — not rated for frequent switching like a contactor, but fine for infrequent disconnect duty. The 20-minute thermal memory means the trip unit remembers prior heating, so a reclose after a near-trip event is safer.

Frequently asked questions

What is C160N45EFM's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

Where can I buy C160N45EFM?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What compliance standards does C160N45EFM meet?

It is designed to EN/IEC 60947-2, with IP40 per IEC 60529 and IK07 per EN 50102. Pollution degree 3 per IEC 60947.

MPN
C160N45EFM