Protection and coordination
The C1644V160: Long-time pickup (Ir) adjusts from 63 to 160 A, with fixed time delays: 400 s at 1.5 x Ir, 16 s at 6 x Ir, and 11 s at 7.2 x Ir. Short-time pickup (Isd) is adjustable from 1.5 to 10 x Ir; instantaneous pickup (Ii) is fixed at 2400 A. Earth-leakage sensitivity (IΔn) and time delay (Δt) are both adjustable.
Mounts fixed in a ComPacT NSX100...250 breaker. IP40 front face. Neutral position left, with protected pole options 3D + N/2, 4D, or 3D.