Skip to main content
Schneider Electric C16B47E100 — Residual Current Breakers (RCCB/RCBO)

Schneider Electric C16B47E100 ComPacT NSX160B, 100 A, 40 kA

MPNC16B47E100
Obsolete

Schneider Electric ComPacT NSX, NSX160B, C16B47E100, 100 A at 40 °C, 40 kA Icu at 240 V AC, MicroLogic 7.2 E trip unit, 4P.

$1,642.73 – $3,674.16Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16B47E100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16B47E100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (operating cycles)40000 cycles
C16B47E100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX160B
C16B47E100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C16B47E100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C16B47E100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C16B47E100 is a Schneider Electric ComPacT NSX160B moulded-case circuit breaker with a MicroLogic 7.2 E electronic trip unit, rated 100 A at 40 °C. The 40 kA Icu at 240 V AC (25 kA at 415 V, 20 kA at 440 V, 15 kA at 500 V) per IEC 60947-2 tells you the maximum fault current this breaker can safely interrupt at those voltages — critical for verifying the available fault current at the panelboard doesn't exceed the rating. The 4-pole (4P) configuration with left-side neutral suits distribution boards where the neutral is switched alongside the phases. The MicroLogic 7.2 E trip unit provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection — all adjustable via the LCD display and toggle controls. This matters for motor or transformer feeders where repetitive starting can heat the cable.

Mounts on a backplate (flat on the back) in horizontal or vertical orientation.

Durability and duty cycles

Mechanical durability is 40,000 cycles. Electrical durability varies with load: 40,000 cycles at 440 V at half rated current (In/2), 20,000 cycles at 440 V at full In, 15,000 cycles at 690 V at In/2, and 7,500 cycles at 690 V at full In. For distribution applications where the breaker is switched infrequently, these cycle counts are generous; for frequent switching (e.g., capacitor bank or lighting contactor duty), the electrical endurance at the actual load current should be checked against the switching frequency.

Frequently asked questions

Where can I buy C16B47E100?

The C16B47E100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C16B47E100 at different voltages?

The breaking capacity (Icu) per IEC 60947-2 is 40 kA at 220/240 V AC, 25 kA at 380/415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC, all at 50/60 Hz.

What protection functions does the MicroLogic 7.2 E trip unit provide?

The MicroLogic 7.2 E provides L (long-time overload), S (short-time short-circuit), I (instantaneous short-circuit), and R (earth-leakage) protection, all adjustable via the LCD display.

What standards does C16B47E100 comply with?

The C16B47E100 complies with EN/IEC 60947-2 for low-voltage switchgear and controlgear. Pollution degree 3 per IEC 60664-1 covers industrial environments.

MPN
C16B47E100