Skip to main content
Schneider Electric C16F32D160 — Miniature Circuit Breakers (MCB)

Schneider Electric C16F32D160 ComPacT NSX160F, 160 A, 36 kA

MPNC16F32D160
Active

Schneider Electric ComPacT NSX160F, C16F32D160, 3P, 160 A at 40 °C, MicroLogic 2.2 electronic trip unit, 36 kA Icu at 415 V AC, EN/IEC 60947-2.

$379.44 – $1,064.66Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C16F32D160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16F32D160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration3P
Breaking capacity85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)85 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 22 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 8 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16F32D160 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16F32D160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16F32D160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16F32D160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16F32D160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C16F32D160 is a ComPacT NSX160F 3-pole circuit breaker rated 160 A at 40 °C, fitted with a MicroLogic 2.2 electronic trip unit. It delivers 36 kA Icu at 415 V AC (50/60 Hz) per EN/IEC 60947-2, with a full breaking-capacity curve from 85 kA at 240 V down to 8 kA at 690 V.

Above that, derate per the manufacturer's curve. For a 480 V system, the rating drops to 35 kA Icu; at 600 V it's 10 kA. Mounts on a backplate (not DIN rail) — the 105 mm width, 161 mm height, and 86 mm depth fit standard ComPacT cutouts. IP40 front-of-panel protection (IK07 impact rating) suits enclosed distribution boards; not rated for washdown. The toggle control and front-facing connections (both upside and downside) simplify busbar and cable routing in a panel.

Frequently asked questions

Where can I buy C16F32D160 and how do I get a price?

The C16F32D160 is sourced to order against an RFQ through independent distribution; submit an RFQ for current pricing and availability.

What is C16F32D160's breaking capacity at 415 V?

The C16F32D160 provides 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What trip unit does the C16F32D160 use?

It uses a MicroLogic 2.2 electronic trip unit with L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection.

What is the mechanical durability of this breaker?

The C16F32D160 is rated for 40,000 mechanical cycles and 40,000 electrical cycles at 440 V In/2.

MPN
C16F32D160