It carries a 100 A rated current at 40 °C and a breaking capacity of 70 kA Icu at 415 V AC (50/60 Hz) per EN/IEC 60947-2 — that's the H breaking capacity code, meaning it handles high fault currents typical of industrial distribution panels without cascading upstream.
Breaking capacity varies by voltage: 100 kA at 240 V AC, 70 kA at 415 V, 65 kA at 440 V, down to 10 kA at 690 V. At 480 V AC it's rated 65 kA Icu per UL 60947-4-1. Integrated earth-leakage protection (R function) eliminates the need for a separate RCD module. The toggle control and front connections (upside and downside) simplify panel wiring.