Skip to main content
Schneider Electric C16H3TM080 — Miniature Circuit Breakers (MCB)

Schneider Electric C16H3TM080 ComPacT NSX160H, 80 A, 3P, 70

MPNC16H3TM080
Obsolete

Schneider Electric ComPacT NSX, NSX160H, circuit breaker, 80 A, 3P, TM-D trip unit, 70 kA Icu at 415 V AC, backplate mount.

$288.24 – $825.98Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H3TM080 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16H3TM080 — Ratings
ParameterValue
Rated current (In)80 A at 40 °C
Poles configuration3P
Breaking capacity100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 65 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)100 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 70 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 65 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16H3TM080 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16H3TM080 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16H3TM080 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16H3TM080 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16H3TM080 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

What the 80 A TM-D and 70 kA breaking capacity mean for your panel

The 3-pole (3P) unit is built for distribution duty (EN/IEC 60947-2, Category A) and carries a 70 kA Icu breaking capacity at 415 V AC — the H suffix in the device short name NSX160H. The TM-D trip provides L (thermal overload) and I (magnetic short-circuit) protection in one block; no earth-leakage module is fitted. At 440 V AC the Icu is 65 kA, and at 690 V AC it drops to 10 kA — the rating that governs fit is the one at your system voltage, not the headline 100 kA at 240 V.

The front-face connection pitch is 35 mm, with both upside and downside connections on the front — no rear-access bus required. IP40 front face (IK07 impact rating) suits enclosed distribution boards; the pollution degree 3 rating (IEC 60664-1) means it's designed for industrial environments where conductive pollution can occur. The toggle control is manual, with 40,000 mechanical cycles and electrical durability ranging from 40,000 cycles at 440 V In/2 down to 7,500 cycles at 690 V In.

Power dissipation is 8.06 W per pole — three poles total, so roughly 24 W heat to vent. Operating altitude is 0–2000 m without derating, 2000–5000 m with derating. Relative humidity range 0–95 %.

Frequently asked questions

What is C16H3TM080's breaking capacity at 415 V AC?

70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2. At 440 V it is 65 kA, and at 690 V it is 10 kA. The rating that governs your coordination study is the one at your system voltage.

MPN
C16H3TM080