The C16H42D160 is a ComPacT NSX160H 4-pole MCCB rated 160 A at 40 °C with a MicroLogic 2.2 electronic trip unit. At 480 V AC the rating holds at 65 kA Icu (UL 60947-4-1), so it stays usable on 480 V services common in North American plants. The MicroLogic 2.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection curves. Mounts on a backplate in horizontal or vertical orientation (flat on the back). IP40 enclosure protection is fine for clean indoor panels; IK07 impact rating handles accidental tool drops during maintenance.
Selectivity and coordination
For applications requiring zone-selective interlocking or ST delay, a Category B breaker (MicroLogic 5/6 trip units) would be the correct choice. The 4-pole configuration (switched neutral on the left) suits 3-phase + N distribution where the neutral must be protected or switched.