Skip to main content
Schneider Electric C16H44V100 — Residual Current Breakers (RCCB/RCBO)

C16H44V100 ComPacT NSX160H 100A 4P MCCB, 70kA 415V AC

MPNC16H44V100
Active

Schneider Electric ComPacT NSX160H, 4P MCCB, 100 A at 40 °C, MicroLogic 4.2 electronic trip unit, 70 kA Icu at 415 V AC, EN/IEC 60947-2.

$1,252.47 – $2,682.18Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H44V100 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16H44V100 — Electrical Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (operating cycles)40000 cycles
C16H44V100 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX160H
C16H44V100 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C16H44V100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C16H44V100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C16H44V100 is a ComPacT NSX160H 4-pole moulded-case circuit breaker (MCCB) with an electronic MicroLogic 4.2 trip unit, rated 100 A at 40 °C. The 4P configuration with left-side neutral and front-front connections suits standard backplate mounting in switchboards or distribution enclosures.

Protection profile and trip unit

The MicroLogic 4.2 electronic trip unit provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection. The earth-leakage protection is integrated, using the IΔn rotary switch to set the operating mode to OFF.

Breaking capacity across voltage levels

The NSX160H frame delivers 100 kA Icu at 220/240 V AC, 70 kA at 380/415 V AC, 65 kA at 440 V AC, 50 kA at 500 V AC, 35 kA at 525 V AC, and 10 kA at 660/690 V AC, all per IEC 60947-2. Under UL 60947-4-1, it achieves 85 kA at 240 V AC, 65 kA at 480 V AC, and 10 kA at 600 V AC. This voltage-dependent curve means the SCCR you can claim in a panel depends on the line-to-line voltage at the breaker terminals — at 480 V AC, the 65 kA figure is the one to coordinate with downstream devices.

Durability and environmental ratings

Mechanical durability is 40,000 cycles; electrical durability varies by load: 40,000 cycles at 440 V at half rated current, 20,000 cycles at 440 V at full rated current, 15,000 cycles at 690 V at half current, and 7,500 cycles at 690 V at full current. The enclosure is rated IP40 (finger-safe, no water ingress) and IK07 (impact resistance up to 2 J).

Frequently asked questions

What is C16H44V100's breaking capacity at 415 V AC?

The C16H44V100 has a breaking capacity of 70 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What protection functions does the MicroLogic 4.2 trip unit provide?

The MicroLogic 4.2 provides L (long-time overload), So (short-time short-circuit with fixed delay), I (instantaneous short-circuit), and R (earth-leakage) protection.

Where can I buy C16H44V100?

C16H44V100 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN