Skip to main content
Schneider Electric C16H47E160 — Residual Current Breakers (RCCB/RCBO)

Schneider C16H47E160 ComPacT NSX MCCB, 4-pole, 160 A, 100 kA

MPNC16H47E160
Obsolete

Schneider C16H47E160 Compact Nsx, New Generation — now discontinued, supplied from remaining surplus and broker stock.

$1,714.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16H47E160 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16H47E160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description4P
Neutral pole positionLeft
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (operating cycles)40000 cycles
C16H47E160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX160H
C16H47E160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C16H47E160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C16H47E160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C16H47E160 is a Schneider ComPacT NSX molded case circuit breaker rated 160 A at 40 °C with a 100 kA breaking capacity at 440 V AC, built on a 4-pole frame. It carries the MicroLogic 7.2 E electronic trip unit combining overload (L), short-time (S), instantaneous (I), and earth-leakage (R) protection, plus an integrated energy meter and LCD display for real-time power quality data.

Compared to the 3-pole C16H3 basic frame, the C16H47E160 adds a fourth pole and raises the breaking capacity from 10 kA to 100 kA, making it the correct choice when the BOM specifies 4-pole distribution with high fault current capability.

MPN
C16H47E160