Schneider Electric C16N42D100 — Miniature Circuit Breakers (MCB)

C16N42D100 ComPacT NSX Circuit Breaker, 100 A, 90 kA

MPNC16N42D100
Active

Schneider Electric ComPacT NSX circuit breaker, 100 A, 90 kA Icu at 240 V AC, MicroLogic 2.2 electronic trip unit, 4 poles, EN/IEC 60947-2.

$522.15 – $1,292.22Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C16N42D100 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N42D100 — Ratings
ParameterValue
Rated current (In)100 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N42D100 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N42D100 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16N42D100 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N42D100 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N42D100 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range40...100 A
Trip unit protection functionsLSoI

Product details

The C16N42D100 is a Schneider Electric ComPacT NSX circuit breaker, 4-pole, rated 100 A at 40 °C with a MicroLogic 2.2 electronic trip unit. It carries a 90 kA Icu breaking capacity at 240 V AC and 50 kA at 415 V AC, per EN/IEC 60947-2. The N breaking capacity code (50 kA at 415 V AC) tells you this is the standard-interrupting version of the NSX160N frame — sized for distribution panels where fault levels sit in that range, not the high-fault H or L versions.

The MicroLogic 2.2 electronic trip unit gives you L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous) protection curves. That So function with fixed delay is key for selective coordination downstream: you can set the short-time pickup and let a fault clear closer to the load before this breaker opens, keeping upstream feeders alive.

The 140 mm width, 161 mm height, and 86 mm depth fit standard distribution panel footprints. Front connections top and bottom; neutral on the left. IP40 enclosure protection (IK07 impact resistance) means it's suited for indoor panel installation where tools and accidental contact are the main concern, not washdown. The 35 mm connection pitch matches standard busbar and cable lug spacing.

Durability and duty

Mechanical durability is 40,000 cycles; electrical durability varies by load — 40,000 cycles at 440 V at half rated current, 20,000 at full 100 A, and 7,500 at 690 V. That's a solid service life for a distribution breaker in a panel that sees regular switching, not daily operation.

Frequently asked questions

How do I get current pricing and availability for C16N42D100?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is the breaking capacity of C16N42D100 at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz, conforming to IEC 60947-2. The N breaking capacity code means 50 kA at 415 V AC is the standard rating for this frame.

What protection curves does the MicroLogic 2.2 trip unit provide?

L for overload protection (long time), So for short-time short-circuit protection with fixed delay, and I for instantaneous short-circuit protection. The So fixed-delay function enables selective coordination with downstream breakers.

What standards does C16N42D100 comply with?

EN/IEC 60947-2 for low-voltage switchgear and controlgear. Pollution degree 3 per IEC 60664-1 and overvoltage category III. IP40 enclosure protection, IK07 impact resistance.

MPN