Skip to main content
Schneider Electric C16N42D160 — Miniature Circuit Breakers (MCB)

Schneider Electric C16N42D160 ComPacT NSX160N, 160 A, 90 kA,

MPNC16N42D160
Obsolete

Schneider Electric ComPacT NSX series, NSX160N, circuit breaker, 160 A, 90 kA Icu at 240 V AC, 4 poles, MicroLogic 2.2 electronic trip unit.

$522.84 – $1,404.54Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N42D160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N42D160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2 85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1 50 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1 10 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N42D160 — Protection
ParameterValue
Trip unit technologyElectronic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N42D160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
Local signalling/indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C16N42D160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N42D160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N42D160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range63...160 A
Trip unit protection functionsLSoI

Product details

The Schneider Electric C16N42D160 is a ComPacT NSX160N moulded case circuit breaker rated 160 A at 40 °C, 4 poles, with a MicroLogic 2.2 electronic trip unit. It is designed for distribution applications and carries a 90 kA Icu breaking capacity at 240 V AC (50/60 Hz) per IEC 60947-2, stepping down to 50 kA at 415 V and 10 kA at 690 V. The N breaking capacity code means 50 kA at 415 V AC, which is the standard rating for this frame size in most panelboard and switchboard installations. It is electronic, not thermal-magnetic, so it holds calibration better across ambient temperature swings and offers a 20-minute thermal memory before and after tripping — meaning if a downstream fault clears and the breaker resets, the memory prevents immediate re-trip from residual heat, which is useful on motor-starting or welding circuits.

The 90 kA Icu at 240 V AC is the maximum interrupting rating; at typical 480 V industrial supply the breaker is rated 50 kA (per UL 60947-4-1) or 50 kA at 380/415 V AC per IEC. That is sufficient for most low-voltage distribution boards with a transformer impedance of 5–6% and a fault current under 50 kA. The utilisation category is A, meaning it is not intended for frequent switching of motor loads under load; use a contactor for that duty.

Neutral is on the left. IP40 front face; IK07 impact rating.

Frequently asked questions

What is C16N42D160's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC per IEC 60947-2, which matches the N breaking capacity code.

Where can I buy C16N42D160?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What protection functions does the MicroLogic 2.2 trip unit provide?

L (long-time overload), So (short-time short-circuit with fixed delay), and I (instantaneous short-circuit).

What compliance documentation does Schneider provide for C16N42D160?

The breaker is certified to EN/IEC 60947-2 and UL 60947-4-1. Pollution degree 3 per IEC 60664-1. RoHS and REACH declarations are standard for Schneider active products; consult your RFQ for specific documentation needs.

MPN