Skip to main content
Schneider Electric C16N4TM080C — Miniature Circuit Breakers (MCB)

Schneider Electric C16N4TM080C ComPacT NSX160N, 80 A, 50 kA

MPNC16N4TM080C
Active

Schneider Electric, ComPacT NSX, MCCB, C16N4TM080C, 80 A TM-D trip unit, 50 kA Icu at 415 V AC, 4P, toggle control.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C16N4TM080C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C16N4TM080C — Ratings
ParameterValue
Rated current (In)80 A at 50 °C
Poles configuration4P
Breaking capacity90 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)90 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 36 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2 35 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2 10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C16N4TM080C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)40000 cycles at 440 V In/2 20000 cycles at 440 V In 15000 cycles at 690 V In/2 7500 cycles at 690 V In
Mechanical durability (cycles)40000 cycles
C16N4TM080C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C16N4TM080C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C16N4TM080C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C16N4TM080C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The 4-pole (4P) configuration with neutral on the left handles three-phase plus neutral circuits common in European industrial panels. For a 80 A feeder, that means it protects cable and downstream equipment against sustained overloads while clearing hard faults fast enough to limit let-through energy. The utilisation category A (non-selectivity for short-circuit with other CBs on the load side) is standard for a distribution breaker — you don't use this as a main incoming device where full selectivity is required.

Mounts on a backplate (flat on the back) in either horizontal or vertical orientation — no DIN-rail clip here, so plan for screw-mounting in the enclosure. The 140 mm width, 161 mm height, 86 mm depth footprint fits standard MCCB cutouts; the 35 mm connection pitch matches busbar or cable-lug spacing. Front connections top and bottom simplify busbar runs and cable dressing inside the panel.

The IK07 impact rating means it survives a 2 J hammer blow typical of installation handling. No earth-leakage protection built in (without); if you need RCD functionality, you add a separate Vigi module or an external RCCB.

Frequently asked questions

Where can I buy C16N4TM080C and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Submit a request for quote — availability and current pricing are confirmed at quote time.

What is C16N4TM080C's breaking capacity at 415 V?

50 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2. That's the maximum fault current it can safely interrupt at that voltage level.

What compliance documentation does this breaker carry?

The C16N4TM080C is certified to EN/IEC 60947-2, rated for isolation per that standard, and carries IP40, IK07, overvoltage category III, and pollution degree 3 ratings.