It is a 4-pole device rated for distribution applications per EN/IEC 60947-2, with a breaking capacity code of N — 50 kA Icu at 380/415 V AC 50/60 Hz. The TM-D trip unit provides L (thermal) protection for overloads and I (magnetic) protection for short circuits.
The interrupting rating varies with system voltage: 90 kA Icu at 220/240 V, 50 kA at 380/415 V, 50 kA at 440 V, 36 kA at 500 V, 35 kA at 525 V, and 10 kA at 660/690 V AC. All values are per IEC 60947-2.
Durability and mounting
Mechanical durability is rated at 40,000 cycles; electrical durability depends on load: 40,000 cycles at 440 V at half rated current, 20,000 at full rated current, and 7,500 cycles at 690 V at full rated current.