Schneider Electric C2536M220 — Residual Current Breakers (RCCB/RCBO)

Schneider C2536M220 MicroLogic 6.2 E-M trip unit, 220 A, 3-pole

MPNC2536M220
Active

Schneider C2536M220 Compact Nsx, New Generation — now discontinued. Supplied from remaining channel stock; full specifications, lifecycle and same-series options are below.

$497.19 – $1,150.59Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C2536M220 — Residual Current Protection
ParameterValue
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 95 % Ith (red) for temperature over set point
C2536M220 — Electrical Ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
C2536M220 — Identification
ParameterValue
Product / component typeTrip unit
Product range / familyComPacT
C2536M220 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C2536M220 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

Overview

The C2536M220 is a Schneider ComPacT NSX MicroLogic 6.2 E-M electronic trip unit rated 220 A at 65 °C for 3-pole fixed-mount circuit breakers. It is designed for motor protection and provides LSIG protection functions — long-time, short-time, instantaneous, and ground-fault — with zone selective interlocking (ZSI) for coordinated fault isolation. The trip unit includes an LCD display for energy metering, time-stamped event logs, and maintenance indicators.

Protection & adjustment

Long-time pickup Ir is adjustable from 100 to 220 A. Long-time delay Tr is adjustable with ranges depending on trip class: 120 s at 1.5 x Ir for class 5, up to 720 s at 1.5 x Ir for class 30. Short-time pickup Isd has 9 adjustable settings with fixed delay Tsd. Ground-fault pickup Ig is adjustable. The trip unit supports motor trip classes 5, 10, 20, and 30, and includes complementary motor protections such as underload, protracted starting, stalled rotor, and current unbalance.

Compliance & environmental

The C2536M220 complies with EN/IEC 60947-2 and is rated Class II (double insulation). The trip unit carries an 18-month warranty.

Metering & display

The integrated LCD display shows energy metering data, instantaneous and demand values, power quality metrics, and maximeters/minimeters. The unit records time-stamped histories and event tables, and provides maintenance indicators. Local signalling includes a flashing green LED for ready-to-operate and a red LED for temperature above 95 % Ith.

MPN
C2536M220