Schneider Electric ComPacT NSX250, TM-D trip unit, 250 A at 50 °C, 3-pole 3D, thermal-magnetic LI protection, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

C253TM250C — Identification
ParameterValue
Product rangeComPacT
Product range (series)ComPacT NSX100...250
Product/component typeTrip unit
Device applicationDistribution
C253TM250C — Ratings
ParameterValue
Poles configuration3P
Rated operational voltage (Ue)690 V AC 50/60 Hz 750 V DC
Network type (AC/DC)AC DC
Network frequency50/60 Hz
C253TM250C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
C253TM250C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60947-1
C253TM250C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C253TM250C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

It provides LI protection — thermal overload (L) via a fixed long-time delay and adjustable magnetic short-circuit (I) pickup from 5 to 10 x In. The 3-pole 3D configuration suits three-phase distribution panels where earth-leakage protection is handled separately or not required.

Rated operational voltage is 690 V AC 50/60 Hz and 750 V DC, so the trip unit handles standard 400/480 VAC distribution as well as DC bus circuits up to 750 V. The long-time protection delay is fixed at 120 to 400 s at 1.5 x In, with a faster 15 s trip at 6 x Ir — that thermal curve is preset and not field-adjustable, so verify coordination with downstream breakers. The instantaneous pickup (Ii) is adjustable from 5 to 10 x In, giving you a 1250 to 2500 A magnetic trip window to avoid nuisance trips on motor inrush while still clearing hard faults.

Integration notes

This is a trip unit, not a complete breaker — it installs into the ComPacT NSX100...250 fixed-mount frame. IP40 front-face protection keeps tools and fingers out but is not washdown-rated; keep the panel sealed if installed in wet areas.

Frequently asked questions

Where can I buy C253TM250C and how do I get a price?

The C253TM250C is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for your required quantity.

What is C253TM250C's listed range and standards?

The C253TM250C belongs to the ComPacT NSX100...250 range and is certified to EN/IEC 60947-2 for circuit-breaker performance and safety.