Schneider Electric C25B44V100

Schneider Electric C25B44V100 ComPacT NSX 100 A, 40 kA MCCB

MPN C25B44V100
Active

Schneider Electric ComPacT NSX, C25B44V100, 100 A at 40 °C, 4P, 40 kA Icu at 240 V AC, MicroLogic 4.2 electronic trip unit, integrated earth-leakage protection, IP40.

$1,302.87 – $2,605.50 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

C25B44V100 key specifications
ParameterValue
Control typeToggle
Trip unit typeElectronic
Main product or component typeEarth leakage circuit breaker
Voltage440 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
IP ratingIP40
Terminal pitch35 mm
Connection surface topFront
Connection surface bottomFront
Temp storage max85 °C
Temp storage min-50 °C

All specifications

C25B44V100 additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-25 °C
Storage temperature-50...85 °C
Pollution degreeclass 3
Depth86 mm
Width140 mm
Height161 mm
Electrical life cycles20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical life cycles20000 cycles
ApplicationDistribution
Operating temperature-25...70 °C

Product details

The Schneider Electric C25B44V100 is a ComPacT NSX moulded-case circuit breaker rated 100 A at 40 °C, 4-pole, with a MicroLogic 4.2 electronic trip unit and integrated earth-leakage protection. Its 40 kA Icu at 220/240 V AC (25 kA at 415 V) per IEC 60947-2 means it can safely interrupt fault currents up to that level on a 240 V distribution board without needing an upstream current-limiting fuse — a common spec for main or feeder breakers in commercial and light industrial panels.

The 20-minute thermal memory before and after tripping means the breaker remembers prior heating events, so repeated overloads close together trip faster — important for motor or transformer circuits that see inrush.

IP40 enclosure protection means it is suited for clean indoor panels — not washdown or outdoor use. The 35 mm connection pitch and front-facing terminals simplify busbar and cable routing in a distribution board. IK07 impact resistance handles incidental tool contact during panel assembly.

MPN
C25B44V100