It is a 4-pole breaker (4P) with toggle control, designed for distribution applications per EN/IEC 60947-2.
Breaking capacity across common voltages
This breaker's interrupting capacity varies with system voltage: 40 kA Icu at 240 V AC, 25 kA at 415 V AC, 20 kA at 440 V AC, and 15 kA at 500 V AC. The 25 kA at 415 V AC is the rating most often quoted for European 400 V distribution; the 40 kA at 240 V AC covers North American 240/120 V split-phase or 240 V delta services.
Mounts on a backplate — no DIN rail here, so plan for a panel cutout or mounting bracket. It can be installed horizontally or vertically, flat on the backplate. The connection pitch is 35 mm, and both line and load connections are front-facing, which keeps wiring accessible inside the enclosure. IP40 protection means it is okay for clean indoor panels but not washdown areas or dusty environments.