Skip to main content
Schneider Electric C25B6TM160 — Miniature Circuit Breakers (MCB)

C25B6TM160 ComPacT NSX 160A 4P Circuit Breaker, 40 kA

MPNC25B6TM160
Active

Schneider Electric ComPacT NSX series, C25B6TM160, 160 A thermal-magnetic MCCB, 4 poles, 40 kA breaking capacity at 240 V AC.

$336.46Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25B6TM160 — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25B6TM160 — Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25B6TM160 — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25B6TM160 — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25B6TM160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25B6TM160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25B6TM160 — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

The C25B6TM160 is a ComPacT NSX250B frame molded-case circuit breaker with a 160 A TM-D thermal-magnetic trip unit, 4 poles, rated for distribution duty per EN/IEC 60947-2. At 415 V the breaking capacity drops to 25 kA Icu, and at 440 V to 20 kA Icu; that derating curve is standard for MCCBs and means you size the breaker to the actual line-to-line voltage at the fault point, not the system nominal.

Deployment context

The IP40 front face and IK07 impact resistance are adequate for enclosed panel installation; if the breaker lives in a washdown zone or outdoors, it needs a separate enclosure.

Frequently asked questions

What is the breaking capacity of C25B6TM160 at 415 V?

The C25B6TM160 delivers 25 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, which is the standard rating for a 415 V distribution feeder in most industrial panels.

Where can I buy C25B6TM160 and how is it quoted?

The C25B6TM160 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

MPN