Skip to main content
Schneider Electric C25B6TM160C — Miniature Circuit Breakers (MCB)

Schneider Electric C25B6TM160C ComPacT NSX250B, 160 A, 25 kA

MPNC25B6TM160C
Obsolete

Schneider Electric ComPacT NSX250B, C25B6TM160C, 4P thermal-magnetic circuit breaker, 160 A at 50 °C, 25 kA Icu at 415 V AC, toggle control, EN/IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25B6TM160C — Identification
ParameterValue
Product nameComPacT NSX
Product rangeComPacT
Product/component typeCircuit breaker
Device applicationDistribution
C25B6TM160C — Ratings
ParameterValue
Rated current (In)160 A at 50 °C
Poles configuration4P
Breaking capacity40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated service breaking capacity (Ics)40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2 20 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
Rated operational voltage (Ue)690 V AC 50/60 Hz
Rated insulation voltage (Ui)800 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Network type (AC/DC)AC
Network frequency50/60 Hz
Utilisation categoryCategory A
Overvoltage categoryIII
C25B6TM160C — Protection
ParameterValue
Trip unit technologyThermal-magnetic
Earth-leakage protectionWithout
Suitability for isolationYes conforming to EN/IEC 60947-2
Electrical durability (cycles)20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (cycles)20000 cycles
C25B6TM160C — Mechanical
ParameterValue
Mounting supportBackplate
Control typeToggle
C25B6TM160C — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
C25B6TM160C — Approvals
ParameterValue
StandardsEN/IEC 60947-2
C25B6TM160C — Specifications
ParameterValue
[Ir] long-time protection pick-up adjustment range0.7...1 x In
Trip unit protection functionsLI

Product details

ComPacT NSX250B, 160 A, 25 kA — panel fit and protection

The C25B6TM160C is a Schneider Electric ComPacT NSX250B 4-pole circuit breaker with a TM-D thermal-magnetic trip unit rated 160 A at 50 °C. It delivers 25 kA Icu at 415 V AC (40 kA at 240 V, 20 kA at 440 V, 15 kA at 500 V) per EN/IEC 60947-2, making it a solid fit for distribution panels where the available fault current stays under those thresholds. The 140 mm width and 161 mm height fit standard MCCB cutouts; depth is 86 mm.

For a 160 A feeder in a 415 V panel with an available fault current of 22 kA, this breaker holds selectivity with downstream 63 A and 100 A devices when coordinated per the Schneider selectivity guide. At 440 V the Icu drops to 20 kA, so verify the transformer secondary fault level if the panel runs at that voltage.

Rated for pollution degree 3 (industrial environments with conductive or dry non-conductive pollution) per IEC 60664-1, overvoltage category III. IP40 enclosure protection means it is suitable for clean indoor panels but not washdown areas. Relative humidity 0–95 %. Mechanical durability 20,000 cycles; electrical durability varies by load — 20,000 cycles at 440 V at half rated current, 10,000 at full rated current.

Frequently asked questions

Where can I buy C25B6TM160C?

The C25B6TM160C is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of C25B6TM160C at 415 V?

The C25B6TM160C delivers 25 kA Icu at 380/415 V AC 50/60 Hz per EN/IEC 60947-2. At 240 V it is 40 kA, at 440 V it is 20 kA, and at 500 V it is 15 kA.

What standards does C25B6TM160C comply with?

The C25B6TM160C complies with EN/IEC 60947-2 and is suitable for isolation per that standard. Pollution degree 3 per IEC 60664-1, overvoltage category III.

MPN