The TM-D trip unit provides thermal overload protection (L) and magnetic short-circuit protection (I), with the magnetic pickup fixed at a multiple of In typical for distribution-grade breakers. Breaking capacity varies by voltage: 40 kA at 240 V, 25 kA at 415 V, 20 kA at 440 V, and 15 kA at 500 V.
Mounts on a backplate in horizontal or vertical orientation. Front connections top and bottom. The 35 mm connection pitch matches standard busbar systems. Neutral position is left, with neutral protection set to no protection (3D) — verify your system grounding and neutral requirements before specifying.