It carries a B breaking capacity code: 25 kA Icu at 415 V AC, 50/60 Hz, per EN/IEC 60947-2. The 4-pole (4P) design with toggle control suits distribution boards and panel builds where a compact, isolating MCCB is required.
At 220/240 V AC it handles 40 kA; at 440 V AC it drops to 20 kA, and at 500 V AC to 15 kA.
Front connections for both line and load sides. The 4-pole breaker has neutral on the left (3D protection — no neutral protection). IP40 front face, IK07 impact resistance.
Electrical durability depends on load: 20,000 cycles at 440 V at half rated current (In/2), 10,000 cycles at 440 V at full In, 10,000 cycles at 690 V at In/2, and 5,000 cycles at 690 V at full In. Utilisation category A (non-delayed) means it's intended for distribution circuits, not motor starting. The TM-D trip unit is fixed, non-interchangeable in the field — select the rating at ordering.