Skip to main content
Schneider Electric C25F34V160 — Residual Current Breakers (RCCB/RCBO)

C25F34V160 ComPacT NSX 160A Earth Leakage Breaker, 36kA 415V

MPNC25F34V160
Active

Schneider Electric ComPacT NSX, NSX250F, Earth Leakage Circuit Breaker, 3P, 160 A, 36 kA Icu at 415 V AC, MicroLogic 4.2 electronic trip unit.

$1,179.33 – $2,636.28Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

C25F34V160 — Residual Current Protection
ParameterValue
Earth-leakage protection class / typeClass A
Trip unit technologyElectronic
Local signalling / indicationFlashing LED (green) for ready to operate LED 105 % Ir (red) for overload LED 90 % Ir (orange) for overload
C25F34V160 — Electrical Ratings
ParameterValue
Rated current (In)160 A at 40 °C
Rated operational voltage (Ue)440 V AC 50/60 Hz
Poles description3P
Network typeAC
Network frequency50/60 Hz
Rated insulation voltage (Ui)500 V AC 50/60 Hz
Rated impulse withstand voltage (Uimp)8 kV
Overvoltage categoryIV
Electrical durability20000 cycles at 440 V In/2 10000 cycles at 440 V In 10000 cycles at 690 V In/2 5000 cycles at 690 V In
Mechanical durability (operating cycles)20000 cycles
C25F34V160 — Identification
ParameterValue
Product nameComPacT NSX
Product / component typeEarth leakage circuit breaker
Product range / familyComPacT
Device short nameNSX250F
C25F34V160 — Mechanical
ParameterValue
Mounting supportBackplate
Mounting positionHorizontal and vertical Flat on the back
Control typeToggle
C25F34V160 — Environmental
ParameterValue
Operating ambient temperature-25...70 °C
Storage ambient temperature-50...85 °C
IP degree of protectionIP40 conforming to IEC 60529
Pollution degree3 conforming to IEC 60664-1
Relative humidity0...95 %
Operating altitude0...2000 m without derating 2000 m...5000 m with derating
C25F34V160 — Approvals
ParameterValue
StandardsEN/IEC 60947-2

Product details

The C25F34V160 is a Schneider Electric ComPacT NSX earth leakage circuit breaker in the NSX250F frame, rated 160 A at 40 °C with a MicroLogic 4.2 electronic trip unit. It is a 3-pole unit (3P) designed for distribution applications, integrating earth-leakage protection (R) alongside overload (L), short-time short-circuit (So), and instantaneous short-circuit (I) protection. The breaking capacity hits 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2, and 85 kA Icu at 240 V AC per UL 60947-4-1.

The 160 A trip unit rating at 40 °C sets the continuous current limit for a feeder or main in a distribution panel. The integrated earth-leakage protection (R curve) means this single device covers both overcurrent and ground-fault sensing, saving panel space over a separate RCD. Electronic trip unit (MicroLogic 4.2) gives adjustable long-time pickup and delay, plus fixed short-time and instantaneous settings.

Integration notes

The 105 mm width and 161 mm height fit standard ComPacT NSX panel cutouts. The toggle control and local signalling (flashing green LED for ready, red at 105% Ir overload, orange at 90% Ir) give clear status without opening the panel door.

Frequently asked questions

Where can I buy the C25F34V160 and get a price?

The C25F34V160 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the C25F34V160 at 415 V?

The breaking capacity is 36 kA Icu at 380/415 V AC 50/60 Hz per IEC 60947-2.

What standards does the C25F34V160 comply with?

It complies with EN/IEC 60947-2 and UL 60947-4-1.

MPN